SwitchBlade x8112 Chassis Switch Installation Guide
83
Installing the AT-SBxPWRSYS1 System Power Supply
For background information on the AT-SBxPWRSYS1 Power Supply, refer
to “AT-SBxPWRSYS1 Power Supply” on page 49. The chassis must have
at least one AT-SBxPWRSYS1 Power Supply.
Warning
The electronic components in the AT-SBxPWRSYS1 Power Supply
can be damaged by electro-static discharges (ESD). Follow the
procedure in “Protecting Against Electrostatic Discharge (ESD)” on
page 82 to guard against ESD damage when unpacking and
installing the power supply.
To install the AT-SBxPWRSYS1 Power Supply, perform the following
procedure:
1. Choose a slot for the AT-SBxPWRSYS1 Power Supply in the chassis.
You may install it in either slot C and D, shown in Figure 39. The first
AT-SBxPWRSYS1 Power Supply should be installed in slot D,
because the slot does not have a blank power supply panel.
Figure 39. Power Supply Slots
Caution
The AT-SBxPWRSYS1 Power Supply will not work in slot A or B.
2. If the chassis already has a power supply in slot D, remove the blank
power supply panel from slot C by lifting the blank panel handle and
sliding it out of the slot, as shown in Figure 40 on page 84.