20 SwitchBlade 4000 Series Switch
C613-03060-00 REV H
Cooling
•Built-in fan
• Monitoring of PSU fans for stalled or slow speed
LEDs
• Three LEDs indicate power supply status (input, output, and fan status)
• For a complete list of LEDs and their functions, see “LEDs and What
They Mean” on page 47
Electrical Specifications Per Chassis Type
Eight Slot Triple Feed AC Chassis (SB4108-00)
• (100 to 240) V AC (50 to 60) Hz input
For a fully loaded chassis with eight line cards and a fan tray installed
• Maximum continuous current draw for each active PSU, 4 A at 240 V,
8 A at 120 V (due to load sharing, redundant PSUs do not add to the
total continuous current drawn).
• Maximum inrush current for each PSU (cold start), 75 A at 240 V, 37 A
at 120 V.
Eight Slot Dual Feed AC Chassis (SB4108-60)
• 200 V to 240 V AC (50 to 60) Hz input
For a fully loaded chassis with eight line cards and a fan tray installed
• Maximum continuous current draw for each active power feed, 8Aat
240 V, 16 A at 120 V.
• Maximum inrush current for each power feed (cold start), 150 A at
240 V, 75 A at 120 V.
Four Slot Dual Feed AC Chassis (SB4104-00)
• 100 V to 240 V AC (50 to 60) Hz input
For a fully loaded chassis with eight line cards and a fan tray installed
• Maximum continuous current draw for each active power feed, 8A at
240 V, 16 A at 120 V.
• Maximum inrush current for each PSU (cold start), 75 A at 240V, 37 A at
120V.
Eight Slot Dual Feed DC Chassis (SB4108-80)
Fully loaded chassis with four line cards and a fan tray installed
• Maximum continuous current draw for each active power feed, 30A
within the rated input voltage range.
• Maximum inrush current for each PSU (cold start), A within the rated
input voltage range.
• Accepts positive or negative earthing (grounding)